Chess Flameproof - flameproofing forklift trucks, tow tractors, sweepers etc.
home about products & services projects Technical data safety commitment contact us

    technical data
    - hazardous areas
    - gas grouping
    - protection techniques
    - equipment
      temperature ratings

    - equipment standards
    - area classification
      standards

visit the Chess Engineering website



EQUIPMENT TEMPERATURE RATINGS

A major design consideration for modifying equipment for use in hazardous areas is the Equipment Temperature Rating.  Electrical and other equipment must be rated according to the ‘T’ Rating System which certifies that operating temperatures are significantly below the ignition point of particular flammable gases found in hazardous areas.  The T ratings for particular gases and dusts ogether with their maximum  operating temperature are shown below.

GASES AND VAPOURS

GROUP II

Temperature class of equipment
Maximum surface temperature
of equipment  ºC
Minimum ignition temperature
of gas or vapour  ºC
T1
450
450
T2
300
300
T3
200
200
T4
135
135
T5
100
100
T6
85
85

DUSTS

Temperature class of equipment
Maximum surface temperature
of equipment  ºC
Minimum cloud or layer * ignition temperature of dust  ºC
T1
450
525
T2
300
375
T3
200
275
T4
135
210
T5
100
175
T6
85
160

 

* based on practice A of AS/NZS 6124.2.1 equipment for dust layers up to 5mm thick